CKG4-12/160,250,400,630-5 AC High Voltage Vacuum Contactor

Kufotokozera Kwachidule:


Tsatanetsatane wa Zamalonda

Zolemba Zamalonda

Main Technical Parameters
Chitsanzo

CKG4-160-630/12-5

Main circuit rated voltage (KV)

12

12

12

12

Chigawo chachikulu chovotera pano (A)

160

250

400

630

Kuthekera kwakukulu kwapang'onopang'ono (A/100 Ops.)

1600

2500

4000

6300
Kuthekera kwakukulu kwapang'onopang'ono (A/25 Ops.)

1280

2000

3200

5000
Kuthekera kwakukulu kopuma (A/3 Ops.)

3200

3200

4000

6300
Moyo wamakina (Ops.)

1000000

1000000

1000000

1000000

Mphamvu yolimbana ndi mphamvu yamagetsi pa main circuit (kV)

42

42

42

42

Mphamvu yolimbana ndi ma voliyumu a ouxillary circuit (kV)

2.5

2.5

2.5

2.5

Mphamvu yamagetsi yolimbana ndi ma voltage pa control circuit (kV)

2

2

2

2

Mafupipafupi ogwiritsira ntchito (Ops./h)

300

300

300

300

Nthawi yotsegulira (ms)

≤120

≤120

≤120 ≤120
Nthawi yotseka (ms)

≤150

≤150

≤150

≤150
Chilolezo pakati pa otsegula (mm)

5 ± 0.5

5 ± 0.5

5 ± 0.5

5 ± 0.5
Kuyenda (mm)

≥1.2

≥1.2

≥1.2

≥1.2

Miyeso ya Outline ndi Installation

sdf

 


  • Zam'mbuyo:
  • Ena: