ZW32-24 panja HV vacuum circuit breaker ndi 3-phase AC 50Hz 24kV zida zosinthira panja.

♦ Njira yoyika: yokwera;

♦ Njira yogwiritsira ntchito: njira yogwiritsira ntchito masika ndi makina ogwiritsira ntchito maginito osatha;

♦ Mtundu wa pole: mzati wophatikizika;

♦ Kugwiritsa ntchito: panja 24kV substation, malo opangira magetsi.

♦ Mtundu wa ntchito, buku, magetsi, mphamvu yakutali.

Miyezo ya Zamalonda

♦ IEC62271-100 High Voltage Switchgear ndi Controlgear Gawo 100: AC Circuit-breakers

♦ GB1984 High Voltage AC zophwanya Madera

♦ Zodziwika bwino za GB/T11022 za High-voltage Switchgear ndi Controlgear

Miyezo

♦ JB/T 3855 High Voltage AC Vacuum Circuit-breakers

♦ DL/T402 Mafotokozedwe a High-voltage AC Circuit-breakers

Mikhalidwe Yachilengedwe

♦ Kutentha kozungulira: -35°C~+40 ° C;

♦ Kutalika:

♦ Kuthamanga kwa mphepo

♦ Kuchuluka kwa chivomezi:

♦ Mulingo wonyansa: IV;

♦ Malo oyika: Palibe ngozi ya moto, kuphulika kapena zonyansa kwambiri.

Main Technical Parameters

Ayi

Kanthu

Chigawo

Mtengo

1 Adavotera mphamvu

kV

makumi awiri ndi mphambu zinayi

2 Zovoteledwa panopa

A

630/1250

3 Adavoteledwa pafupipafupi

Hz

50

4 Adavotera matenthedwe

kA

20/25

5 Idavoteredwa ndi break circuit breaking current

kA

20/25

6 Adavotera dynamic current (pamwamba)

kA

50/63

7 Kutsekera kwakanthawi kochepa (pamwamba)

kA

50/63

8 Kutentha nthawi yokhazikika

s

4

9 Adavoteledwa kachitidwe

Nthawi

O-0.3S-CO-1 80S-CO

10

1 mphindi mphamvu pafupipafupi kupirira voteji (pakati-gawo, dziko lapansi / kusweka)

kV

65

Mphamvu ya mphezi imapirira mphamvu (pamwamba) (pakati pagawo, dziko lapansi / kusweka)

125

Sekondale dera 1min mphamvu pafupipafupi kupirira voteji

2

 

Ayi

Kanthu

Chigawo

Mtengo

11

Moyo wamakina Nthawi

10000

12

Idavotera nthawi yakusweka kwakanthawi kochepa Nthawi

30

13

Zovoteledwa nthawi zosweka Nthawi

10000

14

Kulumikizana kutali

mm

12 ±1

15

Paulendo

mm

3 ±1

16

Inter-phase center mtunda

mm

380±1.5

17

Kutseka kwa magawo atatu ndi kutsegula asynchronism

Ms

≤2

18

Nthawi yotseka yolumikizirana

Ms

≤2

19

Nthawi yotseka

Ms

25-80

20

Nthawi yotsegulira

Ms

23-50

makumi awiri ndi mphambu imodzi Kuthamanga kwapakati

Ms

1.1-1.7

makumi awiri ndimphambu ziwiri Avereji yotseka liwiro

Ms

0.5-0.9

makumi awiri ndi mphambu zitatu

Main conductive dera kukana

≤80

Kujambula Kwazonse Zazikulu ndi Kuyika (gawo: mm)

svv

1. Chingwe chapamwamba chotuluka 2. Chosokoneza 3. Chotsekera chubu 4. Chingwe chotsika chotsika

5. Makonda clip 6. Flexible kugwirizana 7. Insulating lever 8. Contact kuthamanga kasupe

9. Kutsegula kasupe 10. Kuyendetsa 11. Njira yotuluka shaft 12. Njira yogwiritsira ntchito

13. Bokosi la Mechanism 14. Bokosi lamakono la transformer

ndi zina

1. Chogwirira ntchito 2. Lumikizani shaft yayikulu 3. Chigwiriro chotsegula / kutseka

4. Chogwirira chosungira mphamvu 5. Kutsegula/kutseka chizindikiro 6. Pulagi yolumikizira 7. Transformer yamakono

8. Insulator 9. Chotsekera chimango 10. Chingwe chotchinga 11. Malo olowera mzere

12. Chotsani tsamba 13. Potuluka mzere wodutsa 14. Wothyola dera

 

Njira zoyikapo (ndondomeko imodzi/ndondolo iwiri)

svv

 


  • Zam'mbuyo:
  • Ena: